DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.WHAT TO DO IF YOU SMELL GAS:• Do no
XDV Direct Vent Gas Fireplace1010009383The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in
10009383 11XDV Direct Vent Gas FireplaceThis appliance may be fitted with a Synetek ignition module. Installation of the remote on/off starter switch o
XDV Direct Vent Gas Fireplace1210009383Optional Top Vent ApplicationThe 33/36/39XDV fireplaces are shipped as rear vent units. If the layout requires a
10009383 13XDV Direct Vent Gas FireplaceTop Vent ApplicationRestrictor PlateWhen the 33XDV or 36XDV models are installed as top vent fireplaces with a
XDV Direct Vent Gas Fireplace1410009383VVVVVVVXXXDEBBBCBMBAJKFLVENT TERMINATION AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTEDHIOper
10009383 15XDV Direct Vent Gas FireplaceGeneral Information Assembling Vent PipesCanadian Installations:Venting system must be installed in accordance
XDV Direct Vent Gas Fireplace1610009383The vent chart should be read in conjunction with the following vent installation instructions to determine the
10009383 17XDV Direct Vent Gas FireplaceDVR584-600Rear vent no elbows2/99 djt20" (508 mm)Rear Vent Top ViewDVR584-600Fig. 21 Rear vent applica
XDV Direct Vent Gas Fireplace1810009383FP1005Side View Vent Termination1/25/00 djtFinished WallVent TerminationFP1005Fig. 25 Side view of final unit
10009383 19XDV Direct Vent Gas Fireplace• The maximum number of 90° elbows per side wall installation is three (3). (Fig. 28)• If a 90° elbow is fitt
XDV Direct Vent Gas Fireplace210009383PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.Thank you and congratulations o
XDV Direct Vent Gas Fireplace2010009383Vertical Sidewall InstallationTwist Lock PipeSTEP 1Locate vent opening on the wall. It may be necessary to firs
10009383 21XDV Direct Vent Gas FireplaceSTEP 7Apply high temperature sealant to 4” (102 mm) and 7” (178 mm) collars or the termination one inch away f
XDV Direct Vent Gas Fireplace2210009383Below Grade InstallationsWhen it is not possible to meet the required vent ter-minal clearances of 12” (305 mm)
10009383 23XDV Direct Vent Gas FireplaceMax. Height 40’ (12.2m)Min. Height 8’ (2.4m)Max. 10’ (3m)Support Straps Every 3’ (.9m)Max. Height 40’ (12.2m)M
XDV Direct Vent Gas Fireplace2410009383FP1184Typical roof/ceilingsupport apps.Typical Roof Support ApplicationTypical Ceiling Support ApplicationFig.
10009383 25XDV Direct Vent Gas Fireplace7TDVRVT - Through the wall Rear Vent Termination Starter Kit - Model 7TDVSK - Sidewall Venting (Twist Lock P
XDV Direct Vent Gas Fireplace2610009383Glass InformationOnly glass approved by CFM Corporation should be used on this fireplace.• The use of any non-a
10009383 27XDV Direct Vent Gas FireplaceLog Center Right (A51)LG955Figure 50Installation of LogsThe logs are fragile an
XDV Direct Vent Gas Fireplace281000938336XDV4. Place the log front (A50). Place the two underside holes of the log over the two pin studs of the brac
10009383 29XDV Direct Vent Gas FireplaceLog Front(B155)LG950Figure 552. Place the log, center right (B153). Place the two
10009383 3XDV Direct Vent Gas FireplaceThis gas appliance should be installed by a qualified installer, preferably NFI or WETT (Canada) certified, in ac
XDV Direct Vent Gas Fireplace3010009383NOTE: Refer to Figure 56 for bracket and bend loca-tions.1. Place the log front right. Hold the log with the p
10009383 31XDV Direct Vent Gas FireplaceLog RearLG467Figure 613. Place log rear. The rear log sits in the firebox at an angle t
XDV Direct Vent Gas Fireplace3210009383Large Lava RockThe large bag of lava rock provided with this fireplace must be placed on the firebox base around
10009383 33XDV Direct Vent Gas FireplaceFig. 68 Correct burner flame appearance.Yellow FlamesRed GlowLG959Yellow FlamesRed Gl
XDV Direct Vent Gas Fireplace34100093833. Open louvre assembly bottom.4. Push in gas control knob slightly and turn clock-wise to “OFF”. Do not
10009383 35XDV Direct Vent Gas FireplaceLighting & Operating Instructions For Fireplaces equipped with SIT822 Gas Valve (EN or EP) A. T
XDV Direct Vent Gas Fireplace3610009383Instructions for RF Comfort Control ValveThe Comfort Control Valve allows remote control of temperature, fan an
10009383 37XDV Direct Vent Gas FireplaceDelay Timer ModeThe shut off delay timer has a maximum of 2 hours and a minimum of zero minutes. To change the
XDV Direct Vent Gas Fireplace3810009383LED Count Service Action 8 Replace valve 7 Confirm stepper motor connection exists 5 Confirm fan conn
10009383 39XDV Direct Vent Gas FireplaceLight pilot burnerSet manual switch to local or remoteRelease pilotstat knobTurn pilotstat knob from PILOT to
XDV Direct Vent Gas Fireplace410009383Requirements for the Commonwealth of MassachusettsAll gas fitting and installation of this heater shall only be d
XDV Direct Vent Gas Fireplace4010009383NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the “On” position.SIT
10009383 41XDV Direct Vent Gas FireplaceTroubleshooting the Gas Control SystemSIT 822 Valve with Synetek Electronic ControlOperating DiagramNormal Ope
XDV Direct Vent Gas Fireplace4210009383Fuel Conversion InstructionsTo convert the XDV units for use with a different gas fol-low these instructions. B
10009383 43XDV Direct Vent Gas Fireplace LP: Rear air shutter fully open. Front air shutter fully open.7. Reinstall burner housing assembly and f
XDV Direct Vent Gas Fireplace4410009383Fuel Conversion InstructionsHoneywell Comfort Control Valve ONLYWARNING: The conversion must only be undertaken
10009383 45XDV Direct Vent Gas FireplaceCO103Gas ConversionAir shutter2/15/99 djtFig. 85 Remove air shutter from burner pan.Shutter Retaining Sc
XDV Direct Vent Gas Fireplace4610009383Conversion to Natural Gas Burner Orifice Input (BTU/hr) Kit # Model Front Part # Rear Part
10009383 47XDV Direct Vent Gas FireplaceBurner and Burner CompartmentIt is important to keep the burner and the burner compartment clean. At least onc
XDV Direct Vent Gas Fireplace4810009383381a1f1d1 33XDV2313193221a,b22a,b2627242528HILO3923a,b31454846494751525361LOCALREMOTEON•PILOTOFF•LED405933a
10009383 49XDV Direct Vent Gas Fireplace33XDV/36XDV/39XDV (continued) Ref. Description 33XDV 36XDV 39XDV 1. Log Set (Complete) 10009399 10009
10009383 5XDV Direct Vent Gas Fireplace Ref. 33XDV 36XDV 39 XDV A 33” (838 mm) 36” (914 mm) 39” (991 mm) B 28⁷⁄₈” (733
XDV Direct Vent Gas Fireplace501000938333XDV/36XDV/39XDV (continued) Ref. Description 33XDV 36XDV 39XDV 33a. Orifice Pilot Nat. RF -- 20000908
10009383 51XDV Direct Vent Gas FireplaceOptional Accessories AvailableFK12 Fan Assembly1. Open louvre assembly bottom.2. Install FK12 fan in back of
XDV Direct Vent Gas Fireplace5210009383Remote ControlsOptional remote control units are available to control dif-ferent functions of the appliance. (F
10009383 53XDV Direct Vent Gas FireplaceOptional Trim KitsLouvre Accent Trim Appliance Model Main Louvre Kit Additional LouvrePolished Brass 36XDV
XDV Direct Vent Gas Fireplace5410009383
10009383 55XDV Direct Vent Gas FireplaceBASIC WARRANTY CFM Corporation (hereinafter referred to collectively as the Company) warrants that your new V
Efficiency Ratings Model EnerGuide Ratings Steady State (%) D.O.E. Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%) 33XDVRN 60.1 80 81 64
XDV Direct Vent Gas Fireplace6100093835/8"V - Rough Opening Width7" Dia.4" Dia.RoughOpeningHeightRoughOpeningDepthRecessedNailing Flang
10009383 7XDV Direct Vent Gas FireplaceTop of Unit to Ceiling ...36” (914 mm)Front of Unit to Combustibles ...
XDV Direct Vent Gas Fireplace810009383A hearth is not mandatory but is recommended for aesthetic purposes. We recommend a noncombustible hearth whic
10009383 9XDV Direct Vent Gas FireplaceGas Line InstallationWhen purging the gas lines, the front win-dow frame assembly must be removed.The gas pipel